All fire hydrants placed in the township in the future shall have the below stated standards:
(A) Minimum size of valve: five and one-quarter inches;
(B) Operating nut size and shape: NFPA Spec. 1.5 pentagon;
(C) Hose nozzle: number two size two and one-half inches thread NSFT;
(D) Pumper nozzles: number one size five-inch Storz;
(E) The pumper connection shall be a brass Storz fire flow nozzle compatible with five-inch Storz coupled large diameter fire hose;
(F) The nozzle shall be an integral part of the fire hydrant assembly, resistant to tamper or removal by persons not familiar with the art of hydrant construction; and
(G) All nozzle caps shall have a NFPA standard one-half inch Pentagon nut.
(Res. 151, passed 12-12-2000)