§ 154.34 JUNCTION BOXES; TRANSFORMER ENCLOSURE.
   (A)   Junction boxes installed on the supply side of conduits extending to underwater pool lights shall be constructed of brass or suitable copper alloy unless located:
      (1)   Not less than 4 feet from the pool perimeter.
      (2)   Not less than 8 inches above the ground or concrete surface.
      (3)   Transformer enclosures shall be approved for use in wet locations, or shall be located:
         (a)   Not less than 4 feet from the pool perimeter.
         (b)   Not less than 12 inches above the ground or concrete surface.
         (c)   In no case less than 12 inches above the maximum water level.
   (B)   Junction boxes shall be provided with means for independently terminating not less than 2 grounding conductors.
('69 Code, § 6-134)