1137.28 WATER SUPPLY.
   (a)   The applicant shall construct a system of water mains and connect with the public water system to supply adequate public water service for each parcel of land to be occupied by a residential, commercial or industrial unit.
   (b)   All water mains for fire protection and local domestic water in public thoroughfares shall be C-909 PVC pressure class 235 or Class 52 cement-lined cast/ductile iron pipe meeting or exceeding Class 52 specifications, as determined by the City Engineer and the Superintendent of the Water Department. Minimum diameter of eight inches shall be required, always with the approval of the City Engineer and the Superintendent of the Water Department.
   (c)   All water mains and appurtenances shall be constructed in accordance with the rules, standards and specifications of the City and the American Water Works Association.
   (d)   All drawings shall show placement of hydrants and size of water mains according to the following specifications:
      (1)   A minimum of two hydrants within 500 feet of any building.
      (2)   No part of a building should be more than 300 feet from a hydrant.
      (3)   Hydrants are to be installed according to City standards.
      (4)   Size of mains:
         A.   Minimum size line to be eight inches or as determined by the Water Division.
         B.   Location of hydrants on the site shall be approved by the Fire Department.
      (5)   Driveway arrangement shall be designed so that fire equipment can reach hydrants by the use of such drives.
(Ord. 16-19. Passed 9-16-19.)