(A) General regulations concerning water supply.
(1) The water supply system of the mobile home parking area shall be connected by pipes to all buildings and other facilities requiring water.
(2) All water piping, fixtures, and other equipment shall be constructed and maintained in accordance with state and local regulations and requirements and shall be of a type and in locations approved by the state’s Division of Health.
(3) The water piping system shall not be connected with non-potable or questionable water supplies and shall be protected against the hazards of backflow or back siphonage.
(4) The system shall be so designed and maintained as to provide a pressure of not less than 20 pounds per square inch, under normal operating conditions, at service buildings and other locations requiring potable water supply.
(B) Location of riser pipes. Riser pipes provided for individual water service connections shall be located within the confined area of the mobile home stand at a point where the water connection will approximate a vertical position.
(C) Height of riser pipes. Water riser pipes shall extend at least four inches above ground elevation. The pipe size shall be at least three-quarter inch. The water outlet shall be capped when a mobile home does not occupy the lot.
(D) Freeze prevention. Adequate provisions shall be made to prevent freezing of service lines, valves, and riser pipes.
(E) Valve regulations. Underground stop and waste valves shall not be installed on any water service.