Sec. 8-15.604. Roofs.
   (a)   Accessible attics shall be insulated to achieve a minimum R-30 insulation value.
   (b)   Attic vents shall be modified as follows:
      (1)   Gable vents or vents that penetrate the roof surface shall be provided with noise control louver vents that meet the noise reduction levels shown in Table 15-A or transfer ducts that are at least six (6) feet in length. The ducts shall be of flexible insulated ducting with a bend so that there is no direct line-of-sight from the exterior through the duct into the attic.
      (2)   Eave vents do not require modification.
   (c)   Roofs with a slope of 2:12 or less and open beam ceilings shall be modified only if bearing walls are adequate to support the additional load stresses:
      (1)   Existing roof covering shall be removed to expose sheathing.
      (2)   Two (2) foot by six (6) foot rafters at twenty-four (24) inches on center shall be installed directly above the existing roof construction and supported by existing bearing walls, shall be insulated with R-19 fiberglass batts, and shall be covered with one-half (½) inch plywood sheathing.
      (3)   New roofing shall be installed on the new construction that can be adequately supported by the new framing and existing bearing walls.