6-2-7-10: GROUND FAULT CIRCUIT INTERRUPTERS:
   A.   Swimming Pools: Ground fault circuit interrupters shall be used on all outlets in all swimming pools, ornamental pools or other similar bodies of water both inside and outside of the building.
   B.   Bathrooms: All bathrooms and powder rooms shall have ground fault circuit interrupter receptacles on a twenty (20) ampere circuit for all outlets. Exhaust fans and lighting shall be connected to the load side of GFCI receptacles on a fifteen (15) ampere circuit to the nearest GFCI receptacle in the bedrooms. Spas, whirlpool tubs, hot tubs and similar bathing fixtures shall have their power supply connected to a GFCI circuit breaker on a separate circuit within the distribution panel.
   C.   Rooftop HVAC Equipment: All rooftop air conditioning units and heating units shall be on a separate GFCI protected receptacle. (Ords. 94-3-8, 01-09-32)