10-5-1-4-2: ELECTRICAL, MECHANICAL, PLUMBING, AND OTHER EQUIPMENT:
Electrical, heating, ventilating, air-conditioning, plumbing, duct systems, and other equipment and service facilities shall be elevated at or above one foot (1') above the base flood level or shall be designed and installed to prevent water from entering or accumulating within the components and to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during conditions of flooding. In addition, electrical, heating, ventilating, air-conditioning, plumbing, duct systems, and other equipment and service facilities shall:
   A.   If replaced as part of a substantial improvement shall meet all the requirements of this section. (Ord. 666-20, 10-13-2020)