155.33 SECTION 903.4.2 - AMENDED - ALARMS.
Section 903.4.2, Alarms, of the IBC, is hereby amended by deleting said section and inserting in lieu thereof the following section:
   Section 903.4.2 Alarms. An approved weatherproof audible device suitable for outdoor use with 110 candela visual signal shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.