1436.10 SPRINKLER SYSTEM CONNECTION THREADS AND CAPS.
   (a)   Every sprinkler system shall be equipped with one or more approved Fire Division connections.
   (b)   There shall be a Fire Division hose connection on each street frontage or, when the building sets back of the street lines, on each accessible exterior wall. However, when a frontage or exterior wall is less than fifty feet in length, no connection will be required on that frontage if the required connections are provided on the other frontages.
   (c)   The thread of such connection shall be uniform with that used by the Fire Division. Substantial caps shall be provided on each connection.
(Ord. 42-1981. Passed 2-23-81.)