§ 51.100 WATER LINE DESIGN.
   (A)   Water lines shall be designed using a “C” equals 140 or less. The minimum size water line with one fire hydrant shall be six inches and with two or more fire hydrants shall be eight inches. All other water lines shall be no less than two inches. All water lines shall have a minimum cover of four feet.
   (B)   The maximum head loss permitted at the design velocity shall be five feet per 1,000 feet of pipe.
   (C)   The minimum residual pressure at the design flow (fire and/or domestic flows as appropriate) at the highest inhabited floor of any building shall be 20 psi.
   (D)   Fire hydrants shall be spaced so that any point of inhabited building can be reached by less than 500 feet of fire hose from the first hydrant and 500 feet of hose from the second hydrant. All fire hydrants shall conform to the village standard drawings.
(Ord. 287, passed 3-12-2024)