§ 92.092 PLANS FOR FIRE PROTECTION EQUIPMENT.
   Plans for fire alarms systems, water-based fire protection systems, fire pumps, special hazard fire suppression systems, high-piled storage arrangements and firestop systems shall be submitted to the City of Noblesville Fire Department prior to the request for a required wall rough inspection. Each respective submittal shall contain the following information:
   (A)   Sprinkler systems:
      (1)   One full set of sprinkler/standpipe plans.
      (2)   One full set of sprinkler/standpipe calculations.
      (3)   One copy of the sprinkler construction design release (CDR).
      (4)   One set of manufacturer’s cut-sheets for all sprinkler heads in the design.
   (B)   Fire alarm systems:
      (1) One full set of fire alarm plans (1/8” - 1’ scale).
      (2)   One set of battery calculations.
      (3)   One copy of the fire alarm construction design release (CDR).
      (4)   One set of manufacturer’s cut-sheets for the fire alarm control panel (FACP) and fire alarm components.
      (5)   One fire alarm performance matrix.
   (C)   Special hazard fire protection systems:
      (1)   One set of plans (if applicable).
      (2)   One set of engineering data (if applicable).
      (3)   One copy of the construction design release (if applicable).
      (4)   One set of manufacturer’s cut-sheets for system components.
   (D)   Fire pumps:
      (1)   One copy of the manufacturer’s fire pump specifications.
      (2)   One copy of the manufacturer’s certified pump test characteristic curve.
   (E)   Firestop systems:
      (1)   Through-penetration firestop systems.
      (2)   Membrane-penetration firestop systems.
      (3)   Fire-resistant joint systems.
      (4)   Perimeter fire barrier systems.
      (5)   Fire-rated duct and air-transfer openings.
(Ord. 50-10-09, passed 10-27-09) Penalty, see § 92.999