Skip to code content (skip section selection)
Compare to:
New York City Overview
The New York City Charter
The New York City Administrative Code
The Rules of the City of New York
THE RULES OF THE CITY OF NEW YORK
Title 1: Department of Buildings
Title 2: Board of Standards and Appeals
Title 3: Fire Department
Title 6: Department of Consumer and Worker Protection
Title 9: Procurement Policy Board Rules
Title 12: Franchise and Concession Review Committee
Title 15: Department of Environmental Protection
Title 16: Department of Sanitation
Title 17: Business Integrity Commission
Title 19: Department of Finance
Title 20: Tax Appeals Tribunal
Title 21: Tax Commission
Title 22: Banking Commission
Title 24: Department of Health and Mental Hygiene
Title 25: Department of Mental Health and Retardation [Repealed]
Title 28: Housing Preservation and Development
Title 29: Loft Board
Title 30: Rent Guidelines Board
Title 31: Mayor's Office of Homelessness and Single Room Occupancy
Title 34: Department of Transportation
Title 35: Taxi and Limousine Commission
Title 38: Police Department
Title 38-A: Civilian Complaint Review Board
Title 39: Department of Correction
Title 40: Board of Correction
Title 41: Department of Juvenile Justice
Title 42: Department of Probation
Title 43: Mayor
Title 44: Comptroller
Title 45: Borough Presidents
Title 46: Law Department
Title 47: Commission on Human Rights
Title 48: Office of Administrative Trials and Hearings (OATH)
Title 49: Department of Records and Information Services
Title 50: Community Assistance Unit
Title 51: City Clerk
Title 52: Campaign Finance Board*
Title 53: Conflicts of Interest Board
Title 55: Department of Citywide Administrative Services
Title 56: Department of Parks and Recreation
Title 57: Art Commission
Title 58: Department of Cultural Affairs
Title 60: Civil Service Commission
Title 61: Office of Collective Bargaining
Title 62: City Planning
Title 63: Landmarks Preservation Commission
Title 66: Department of Small Business Services
Title 67: Department of Information Technology and Telecommunications
Title 68: Human Resources Administration
Title 69: Department of Aging
Title 70: In Rem Foreclosure Release Board
Title 71: Voter Assistance Commission
Title 72: Office of Emergency Management
Title 73: Civic Engagement Commission
§ 908-01 Carbon Monoxide Detectors.
   (a)   Scope. Pursuant to sections 908.7.2 and 908.7.3 of the Building Code (BC), listed carbon monoxide (CO) detectors required to be installed in E, I-2 and I-4 occupancies and in buildings equipped with a fire alarm system that contain Group A-1, A-2, A-3, B or M occupancies, as defined in BC Chapter 3, must be installed in accordance with the requirements of this section.
      (1)   These requirements do not apply to those R-2 occupancies that are adjacent to or above those occupancies classified in this section.
      (2)   Pursuant to BC section 908.7.3.1, existing buildings must comply with the requirements of this subdivision by July 1, 2021.
   (b)   Reference. See § 28-315.11 of the New York City Administrative Code (AC), and BC sections 908.7.2, 908.7.3, 908.7.3.1 and 908.7.4.
   (c)   Group E, I-2 and I-4 occupancies. CO detectors with built-in sounder bases installed in E, I-2 and I-4 occupancies in accordance with BC 908.7.2 must be installed in the following locations:
      (1)   Any room containing carbon monoxide-producing equipment, except kitchens and laboratories.
      (2)   Any corridor on the story where carbon monoxide-producing equipment unit is located, as well as one story above and one story below.
      (3)   Any corridor on the story where enclosed parking or a loading dock is located, as well as one story above and one story below.
   (d)   Group A-1, A-2 and A-3. CO detectors with built-in sounder bases installed in buildings that are equipped with a fire alarm system and that contain A-1, A-2 or A-3 occupancies must be installed in the following locations:
      (1)   Any room containing CO-producing equipment, except kitchens.
      (2)   Any occupiable room or space on the same floor as, one story above, or one story below the CO-producing equipment that is at least 75 square feet and is not provided with mechanical ventilation.
      (3)   Any corridor on the story where enclosed parking or a loading dock is located, as well as one story above and one story below.
      (4)   Any parking attendant's office or booth located within an enclosed garage or loading dock.
      (5)   As an alternative to installation as provided in paragraphs (1) through (4) of this subdivision and subject to the Department's approval, in locations determined by a performance-based design that is in accordance with Section 5.8.5.3.2 of reference standard National Fire Protection Association (NFPA) 720 and approved by the Department.
   (e)   Group B and M occupancies. CO detectors with built-in sounder bases installed in buildings that are equipped with a fire alarm system and that contain Group B or M occupancies must be installed in the following locations:
      (1)   Any room containing CO-producing equipment, except kitchens.
      (2)   Any corridor on the story where carbon monoxide-producing equipment unit is located, as well as one story above and one story below.
      (3)   Any corridor on the story where enclosed parking or a loading dock is located, as well as one story above and one story below.
      (4)   Any parking attendant's office or booth located within an enclosed garage or loading dock.
      (5)   As an alternative to installation as provided in paragraphs (1) through (4) of this subdivision and subject to the Department's approval, in locations determined by a performance-based design that is in accordance with Section 5.8.5.3.2 of reference standard National Fire Protection Association (NFPA) 720 and approved by the Department.
      (6)   Detection zones:
         (i)   Detection zones less than 10,000 square feet. Where carbon monoxide detection is required to be provided in a detection zone having an area less than 10,000 square feet, the carbon monoxide detection shall be placed in a central location within such detection zone.
         (ii)   Detection zones 10,000 square feet or greater. Where carbon monoxide detection is required to be provided in a detection zone having an area 10,000 square feet or greater, carbon monoxide detection shall be placed in a central location within such detection zone and at such additional locations with such detection zone as may be necessary to assure that no point in the detection zone is more than 100 feet from carbon monoxide detection.
      (7)   Definition of detection zone. The term "detection zone" as used in this section means a story of a building.
         Exceptions. 
         (i)   If a story is arranged so that two or more separate carbon monoxide producing HVAC systems are used to serve separate portions of the story, each such portion of the story shall be deemed to be a separate detection zone.
         (ii)   If a portion of a story is used as a garage, the portion used as a garage shall not be deemed to be a detection zone and the portion not used as a garage shall be deemed to be a detection zone; and
         (iii)   If an entire story is used as a garage, such story shall not be deemed to be a detection zone.
   (f)   Equipment shutdown. Activation of a CO detector located at the source of CO-producing equipment must shut down that source. This provision does not apply where the source is a generator.
   (g)   Installation requirements. CO detectors must be installed in accordance with NFPA 720 – 2015 edition, as modified for New York City by this section.
   (h)   Fire alarm control units. The provisions of section 23.8.2.2 of NFPA 72 – 2010 regarding having a separate panel apply to CO detectors.
   (i)   NFPA 720 amendments. Pursuant to § 28-103.19 of the New York City Administrative Code, the New York City modifications to reference standard NFPA 720 – 2015 are as follows:
      (1)   Section 2.1 is revised by adding the following at the end: "Where a referenced publication has been modified for the City of New York by the New York City Building Code, every reference to such publication shall be deemed to include all such modifications."
      (2)   Section 2.2 is deleted and a new section 2.2 is added to read as follows:
         2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.
            NFPA 70â, National Electrical Codeâ, as modified and incorporated into the New York City Electrical Code.
            NFPA 72â, National Fire Alarm and Signaling Code, as modified and incorporated into Appendix Q of the New York City Building Code.
            NFPA 101â, Life Safety Codeâ, as listed in Chapter 35 of the New York City Building Code.
            NFPA 110, Standard for Emergency and Standby Power Systems, as listed in Chapter 35 of the New York City Building Code.
            NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems, as listed in Chapter 35 of the New York City Building Code.
      (3)   Section 2.3.4 is deleted and a new section 2.3.4 is added to read as follows:
         Section 2.3.4 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.
            ANSI/UL 1971, Standard for Safety Signaling Devices for Hearing Impaired, 2002, revised 2013.
            ANSI/UL 2034, Standard for Single and Multiple Station Carbon Monoxide Alarms, as listed in Chapter 35 of the New York City Building Code.
            ANSI/UL 2075, Standard for Gas and Vapor Detectors and Sensors, as listed in Chapter 35 of the New York City Building Code.
      (4)   Section 4.4.1.1 is deleted and a new section 4.4.1.1 is added to read as follows:
         Section 4.4.1.1 Carbon monoxide detection system plans and specifications must be developed in accordance with the New York City Building Code by persons who are New York State Registered Design Professionals and experienced in the proper design, application and testing of carbon monoxide detection systems.
      (5)   Sections 4.4.1.2, 4.4.1.3 and 4.4.1.4 are deleted in their entirety.
      (6)   Section 4.4.2.1 is revised to add the following at the beginning: "Carbon monoxide systems installations must be performed by a New York City Licensed electrical contractor."
      (7)   Section 4.4.3.1 is revised to add the following at the beginning: "Carbon monoxide inspection, testing, maintenance and repair may be performed by a New York City Licensed electrical contractor holding a New York State registration for Business of Installing, Servicing or Maintaining Security or Fire Alarm Systems or by those fire alarm companies holding a New York State registration for Business of Installing, Servicing or Maintaining Security or Fire Alarm Systems. The rules and regulations of the Fire Department shall apply as appropriate."
      (8)   Section 5.8.5.3.1 is amended by substituting 5.8.5.3.1(2) with the following:
         (2)   On every level requiring detection and in every HVAC zone of the space requiring detection.
      (9)   Section 9.4.1.1 is deleted in its entirety.
(Amended City Record 10/10/2019, eff. 11/9/2019; amended City Record 3/2/2021, eff. 4/1/2021)