Review and acceptance by the control authority shall be obtained prior to the discharge into the public sewers by any commercial or industrial class customers of sewage whose wastes have:
(A) Either a BOD content greater than 300 milligrams per liter or a COD greater than 600 milligrams per liter;
(B) A suspended solids content greater than 300 milligrams per liter;
(C) A phosphorus content greater than ten milligrams per liter;
(D) An ammonia content greater than 15 milligrams per liter; or
(E) Other contaminants which from either nature or quantity will:
(1) Interfere with the operations of any portion of the sewage utility;
(2) Pass through the treatment works or otherwise be incompatible with such works; and/or
(3) Prevent the reclamation and/or recycling of municipal wastewaters or sludge.
(Prior Code, § 51.21) (Ord. G-93-5, passed 6-8-1993; Ord. G-17-4, passed 9-12-2017)