1117.15 WATER SUPPLY IMPROVEMENTS AND FIRE PROTECTION.
   The following requirements shall govern water supply improvements:
   (a)   The subdivider shall provide a complete water distribution system, and appropriately spaced fire hydrants and valving. Public water distribution systems shall meet the requirements of the Ohio Environmental Protection Agency.
   (b)   Fire hydrants with two (2) 2½" outlets and one 4½" steamer connection (or approved alternate by the Fire Department) shall be provided by the subdivider in all subdivisions with public water supplies. The hydrants should be located between property lines and curbs with all outlets facing or parallel to the street. Hydrants shall be placed at the corners of all blocks and at mid-block for blocks exceeding 800 feet in length. Hydrants shall also be required at the entrance and end of all cul-de-sacs exceeding 400 feet in length. The maximum spacing for fire hydrants shall be 400 feet for residential areas and 300 feet for commercial and industrial areas. The type of hydrant and control valves and the location of the hydrant shall be approved by the Village Administrator. The minimum size of any water line serving any hydrant shall not be less than eight inches (8") in diameter and should be circulating water lines. The size and location of all water lines should be approved by the Village Engineer and the Board of Public Affairs. The Insurance Services Office of Ohio should also approve the size and location of water lines for commercial and industrial subdivisions.