§ 153.09 SPECIAL PROVISIONS.
   (A)   Receptacles installed on 15 to 20 ampere branch circuits must be of the grounding type in kitchen, basement, laundry, garage, and all damp locations.
   (B)   (1)   It shall be unlawful for any person to exchange or sell installation within the corporate limits of the City, any electrical equipment that requires additional wiring, such as stokers, blowers, air conditioning units, ranges, built-in cooking units, signs, coin operated devices, etc., without listing such apparatus, describing such equipment, complete with the name and address of the purchaser, and the location where the equipment is to be installed.
      (2)   This list to be made available to the Electrical Inspector upon request.
   (C)   Illuminated signs of all types shall have a minimum clearance from the ground or walkway of ten (10) feet and shall not extend more than ten (10) feet out from the property line, nor closer than two (2) feet to the curb line of the street. All signs in alleys and over driveways shall have a minimum clearance of fifteen (15) feet. The sign support shall be of steel sufficient strength to adequately support it under all wind and weather conditions. Guys shall be of chain or galvanized steel cable.
(Prior Code, Art. 7, § 7.9)