9-1-6: AMENDMENTS TO INTERNATIONAL FUEL GAS CODE:
IFGC Section 101.1. IFGC section 101.1 (Title) is amended by the addition of the term "town of Morrison" where indicated.
IFGC Section 404.12. IFGC section 404.12 (Minimum Burial Depth) is amended by the addition of the following: All plastic fuel gas piping shall be installed a minimum of 18 inches (457 mm) below grade.
IFGC Section 404.12.1. IFGC section 404.12.1 (Individual Outside Appliances) is deleted in its entirety.
IFGC Section 406.4.1. IFGC section 406.4.1 (Test Pressure) is amended by changing 3 psig to 10 psig.
(Ord. 357, 10-21-2008; amd. Ord. 477, 8-6-2019)