(A) Fats, grease, oil and sand interceptors shall be provided when, in the opinion of the Sewer Inspector, they are necessary for the proper handling of liquid wastes containing grease in excessive amounts, or any flammable wastes, sand and other harmful ingredients, except that such interceptors shall not be required for private living quarters or dwelling units. All interceptors shall be of a type and capacity approved by the Sewer Inspector and shall be located as to be readily and easily accessible for cleaning and inspection.
(B) Fats, grease, oil and sand interceptors shall be constructed of impervious materials capable of withstanding abrupt and extreme changes in temperature. They shall be of substantial construction, water-tight and equipped with easily removable covers which when bolted in place shall be gas-tight and water-tight.
(C) Where installed, all fats, grease, oil and sand interceptors shall be maintained by the owner, at his or her expense, in continuously efficient operation at all times.
(Ord. 17-1989, passed 12-5-1989)