§ 51.091  PERIODIC TESTING.
   (A)   All testable backflow devices shall be tested and inspected at least annually.
   (B)   Periodic testing shall be performed from a list of certified testers provided by the utility. This testing will be done at the owner’s expense.
   (C)   Any backflow prevention device which fails during a periodic test, will be repaired or replaced. When repairs are necessary, upon completion of the repair the device will be retested at owner’s expense to ensure correct operation. High hazard situations will not be allowed to continue if the backflow prevention device fails the test and cannot be repaired immediately. In other situations, a compliance date of not more than 30 days after the test date will be established. The owner is responsible for spare parts, repair tools, or a replacement device. Parallel installation of two devices is an effective means of the owner ensuring uninterrupted water service during testing or repair of devices and is strongly recommended when the owner desires such continuity.
   (D)   Backflow prevention devices will be tested more frequently than specified in division (A) above, if the utility feels that there is a history of test failures. Cost of additional testing will be borne by the owner.
(Prior Code, § 51.81)  (Ord. 98-229, passed 12-10-1998)