1168.02 ELECTRIC VEHICLE SUPPLY EQUIPMENT AND EVSE SPACES.
   (a)   The minimum size of an EVSE space shall be ten (10) feet in width and twenty (20) feet in length.
   (b)   The EVSE space shall count towards determining the minimum number of off-street parking spaces required by this zoning code for the affected zoning district in accordance with Chapter 1157 of the Codified Ordinances.
   (c)   The maximum number of EVSE spaces on a lot shall be two (2) or five percent (5%) of the total off-street parking spaces for the affected use or zoning district as required in Chapter 1157 of the Codified Ordinances.
   (d)   The EVSE space shall be designated by pavement identification markings and a permanent sign immediately adjacent thereto with a maximum face size of four (4) square feet.
   (e)   EVSE shall be protected by permanent concrete filled bollards a minimum of three (3) feet in height or by full depth concrete curbing a minimum of twelve (12) inches in height.
   (f)   EVSE and any related above-ground infrastructure shall be located a minimum of ten (10) feet from any fire access lane, fire hydrants, or any other fire protection equipment.
   (g)   A fire department emergency power disconnect shall be provided and located within fifty (50) feet of the EVSE and supporting electrical equipment, but no closer than ten (10) feet to any EVSE or cabinet, and shall conform with the following additional requirements:
      (1)   The disconnect shall be mounted at a height of sixty inches above the finished grade level.
      (2)   A sign with a minimum face size of four (4) square feet with a red background and two (2) inch white lettering stating "FD Emergency Shutoff - Electric Vehicle Charging Station" shall be installed at each disconnect.
         (Ord. 23-119. Passed 6-8-23.)