§ 8.20.180 APPENDIX B.
   Table B105.2 of the California Fire Code is amended as follows:
   TABLE B105.2 - REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
 
Automatic Sprinkler System
(Design Standard)
Minimum Fire-Flow (gallons per minute)
Flow Duration (hours)
No automatic sprinkler
Value in Table B105.1(2)
Duration in Table B105.1(2) system
Section 903.3.1.1 of the California Fire Code
50% of the value in Table B105.1(2)a
Duration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the California Fire Code
50% of the value in Table B105.1(2)b
Duration in Table B105.1(2) at the reduced flow rate
For SI: 1 gallon per minute =3.785 L/m.
a.   The reduced fire-flow shall be not less than 1,000 gallons per minute.
b.   The reduced fire-flow shall be not less than 1,500 gallons per minute.
(Ord. 2022-364, passed 11-16-2022)