(A) Section 508.1 of the California Fire Code is deleted in its entirety and replaced with the following:
508.1 General. Where required by other sections of this Code and in all buildings classified as high-rise buildings by the California Building Code, in all buildings greater than 300,000 square feet (27 870m2), and in Group 1-2 occupancies having occupied floors located more than 75 feet above the lowest level of fire department vehicle access, a fire command center for fire department operations shall be provided and comply with Sections 508.1.1 through 508.1.7.
(B) Section 508.1.1 of the California Fire Code is deleted in its entirety and replaced with the following:
508.1.1 Location and access. The fire command center shall be located adjacent to the main lobby and shall be accessible from fire department vehicular access or as approved by the fire Code official. The room shall have direct access from the building exterior at the lowest level of fire department access.
(C) Section 508.1.3 of the California Fire Code is amended to add the following:
508.1.3 Size. The fire command center shall not be less than 0.015 percent of the total building area of the facility served or 200 square feet (19 m2) in area, whichever is greater, with a minimum dimension of 0.7 times the square foot of the room area or 10 feet (3048 mm), whichever is greater.
Where a fire command center is solely required because a building is greater than 300,000 square feet (27 870m2), the fire command center shall have a minimum size of 96 square feet (9 m2) with a minimum dimension of 8 feet (2438 mm) where approved by the fire Code official.