§ 8.20.110 FIRE PROTECTION WATER SUPPLIES.
   (A)   A new Section 507.5.7 is added to Section 507 of the California Fire Code to read as follows:
   507.5.7 Fire hydrant size and outlets. As determined by the fire Code official, fire hydrant sizes and outlets shall be based on the following:
   1.   Residential Standard - one (1) four (4) inch outlet and one (1) two and half (2 %) inch outlet.
   2.   Super Hydrant Standard - one (1) four (4) inch outlet and two (2) two and one half (2%) inch outlet.
   3.   Super Hydrant Enhanced - two (2) four (4) inch outlet and one (1) two and one half (2%) inch outlet.
   (B)   A new Section 507.5.8 is added to Section 507 of the California Fire Code to read as follows:
   507.5.8 Fire hydrant street marker. Fire hydrant locations shall be visually indicated in accordance with Riverside County Fire Department Technical Policy 06-11, as may be amended from time to time. Any hydrant marker damaged or removed during the course of street construction or repair shall be immediately replaced by the contractor, developer or person responsible for removal or damage.
(Ord. 2022-364, passed 11-16-2022)