(A) Section 503.2.1 of the California Fire Code is deleted in its entirety and replaced with the following:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). For additional requirements or alternatives see Riverside County Fire Department Standards and Policies, as may be amended from time to time.
(B) Section 503.2.2 of the California Fire Code is deleted in its entirety and replaced with the following:
503.2.2 Authority. The fire Code official shall be the only authority authorized to designate fire apparatus access roads and fire lanes and to modify the minimum fire lane access widths for fire or rescue operations.
(C) A new Section 503.6.1 is added to Section 503.6 of the California Fire Code to read as follows:
503.6.1 Automatic opener. New motorized gates shall be provided with means to be automatically opened remotely by emergency vehicle in accordance with Riverside County Fire Department standards and Policies, as may be amended from time to time.
Exception: Gates serving individual one- and two-family dwelling parcels.
(D) A new Section 503.7 is added to Section 503 of the California Fire Code to read as follows:
503.7 Loading areas and passenger drop-off areas. On private properties, where fire apparatus access roads are utilized for loading or unloading or utilized for passenger drop-off or pick-up, an additional eight (8) feet of width shall be added to the minimum required width for the fire apparatus access road.