(A) A maximum of 8,100 total lumens per acre or per parcel if under one acre shall be allowed. When lighting is “allowed”, it must be fully shielded if feasible and partially shielded in all other cases, and must be focused to minimize spill light into the night sky and onto adjacent properties.
(B) The requirements for lamp source and shielding of light emissions for outdoor light fixtures shall be:
Lamp Type and Shielding Requirements per Fixture | |
Class I — Lamp Type
| |
Low pressure sodium | Allowed |
Others above 4,050 lumens | Allowed if fully shielded |
Others 4,050 lumens and below | Allowed |
Class II — Parking Lots, Walkways, Security — Lamp Type
| |
Low pressure sodium | Allowed |
Others above 4,050 lumens | Prohibited |
Others 4,050 lumens and below | Allowed |
Class III — Decorative — Lamp Type
| |
Low pressure sodium | Allowed |
Others above 4,050 lumens | Prohibited |
Others 4,050 lumens and below | Allowed |
(Ord. 2009-24, passed 3-3-2009)