TABLE VIII: VARIANCES POSSIBLE FOR SEPTIC SYSTEMS TO SERVE NEW CONSTRUCTION.
Note: When circumstances exist which make impractical full compliance with the requirements of the Ordinance, an applicant may request a variance. Each variance request is reviewed in conjunction with the specific on-site conditions. It should not be assumed that a variance will automatically be granted. The following table provides general guidelines for variances which may be considered for private sewage disposal systems for new construction:
Septic System Component
Minimum Separation with a Variation Granted
Water Line Under Pressure
Dwelling
Property Line
Accessory Structure, Above Ground Swimming Pool,
Criteria
Septic System Component
Minimum Separation with a Variation Granted
Water Line Under Pressure
Dwelling
Property Line
Accessory Structure, Above Ground Swimming Pool,
Criteria
Building Sewer
See Footnote 3 in Table IV
N/A
N/A
5 feet
Amount of area available, location of adjacent dwellings, water wells, etc.
Septic Tank
5 feet
2 1/2 feet
2 1/2 feet
2 1/2 feet
Amount of area available, location of adjacent dwellings, water wells, etc.
Aerobic Treatment Unit
5 feet
2 1/2 feet
2 1/2 feet
2 1/2 feet
Amount of area available, location of adjacent dwellings, water wells, etc.
Distribution or Drop Box
No variance
10 feet 1
2 1/2 feet
5 feet
Amount of area available, soil permeability, site topography, locations of adjacent dwellings, water wells, etc.
Subsurface Seepage System
12 1/2 feet
10 feet 1
2 1/2 feet
5 feet
Amount of area available, soil permeability, site topography, locations of adjacent dwellings, water wells, etc.
1. Typically granted in moderate soil permeabilities where space is limited. Typically not granted in moderately rapid or rapid soil permeabilities, or when the septic system is upgradient of the dwelling.
 
(Ord. O-201711-51-031, passed 11-14-2017)