1119.07 ELECTRIC AND TELEPHONE SERVICE.
   The electrical contractor shall install code approved galvanized conduit of rigid type at a minimum burial depth of twenty-four inches below the finished grade. The initial backfill shall be a minimum depth of twelve inches of sand. The conduit shall run from the Illuminating Company grade level connection chamber to the meter socket and shall conform to specifications of the Illuminating Company. Galvanized conduits of rigid type shall be used for all bends and connections.
   The electrical contractor shall also install in like manner conduit to service telephone lines from the telephone company roadway ground connection to the telephone entrance elf. The installation shall conform to specifications of the telephone company.