§ 154.098 WATER SUPPLY FACILITIES.
   (A)   Individual wells. Wells for individual lots will not be allowed. All properties shall be connected to the village water system.
   (B)   Water mains.
      (1)   All water mains that are to be constructed in the village shall be ductile iron pipe, Class 2, cement lined.
      (2)   The water main shall not be less than eight inches in diameter, and shall have all necessary valves housed within valve vaults having a minimum inside diameter of four feet.
      (3)   The design of the water main layout and appurtenances and the material used shall be subject to the approval of the Village Engineer.
      (4)   The necessary permit shall be obtained from the State Environmental Protection Agency.
   (C)   Fire hydrants. Fire hydrants, subject to the approval of the village, shall be installed throughout the entire subdivision at intervals of not exceeding 300 feet. All fire hydrants shall be equipped with six-inch auxiliary valve and valve box. Fire hydrants shall be East Jordan model BR-5 and shall be equipped with two four-inch “steamer” connections. One “steamer” connection shall be national standard threads, and the other shall be a five-inch Storz connection. The locations for this type of fire hydrant will include all areas.
(2000 Code, § 155.083) (Ord. 1274, passed 9-16-1985; Ord. 3053, passed 4-7-2008) Penalty, see § 154.999