§ 23-602.   Power Pump Installations.
   1.   The base of a power pump installed directly over a well casing or pipe sleeve shall be designed to provide an effective watertight seal with the casing or pipe sleeve.
   2.   All power pumps shall be installed on a firm base in an area free from flooding.
   3.   Where power pumps are installed in pits, the pits shall meet the requirements of § 23-402.8. In addition, the pit shall be ventilated with a pipe of a diameter of at least 1½ inches.
   4.   Location and installations of the pump and all related equipment shall permit convenient access, removal, maintenance and repair.
   5.   The pump suction opening shall be placed at least 2 feet below the maximum drawdown of the water in the well. However, the pump suction opening shall be placed at a sufficient distance from the bottom of the well so as to prevent agitation of accumulated sediment.