(A) All distribution boxes installed in any residential or commercial on-site sewage system in the county shall have a riser that extends to final grade. The lid to the box or riser must be safely secured to prevent accidental entry.
(B) All distribution boxes shall be stabilized so as to prevent movement during installation and operation.
(C) All distribution boxes must have a baffle consisting of a sanitary tee in the vertical position, at least the same diameter as the effluent sewer or effluent force main entering the box. The sanitary tee must extend to within two inches of the bottom of the box and there must be at least one-inch head clearance between the top of the tee and the interior bottom of the lid.
(Ord. 2023-20, passed 11-6-2023)