§ 52.86 INSPECTION; MAINTENANCE; TESTING; RECORDS.
   (A)   It shall be the duty of the consumer at any premises on which backflow prevention devices required by these regulations are installed to have inspection, tests, maintenance and repair made in accordance with the following schedule or more often where inspections indicate a need or are specified in manufacturer's instructions.
      (1)   Fixed proper air gap separations shall be inspected to document that a proper vertical distance is maintained between the discharge point of the service line and the flood level rim of the receptacle at the time of installation and at least annually thereafter. Corrections to improper or by passed air gaps shall be made within 24 hours.
      (2)   Double check valve assemblies shall be inspected and tested at the time of installation and at least annually thereafter, and required service performed within five days.
      (3)   Reduced pressure principle backflow prevention assemblies shall be tested at the time of installation and at least annually or more frequently if recommended by the manufacturer, and required service performed within five days.
   (B)   Testing shall be performed by a person who is approved as competent to service the device. Proof of approval shall be in writing. Each test result will be sent to the city Water Superintendent.
   (C)   Each device shall have a tag attached listing the date of most recent test or visual inspection, name of tester, and type of date of repairs.
   (D)   A maintenance log shall be maintained and include:
      (1)   Date of each test or visual inspection;
      (2)   Name of approval number of person performing the test or visual inspection;
      (3)   Test results;
      (4)   Repairs or servicing required;
      (5)   Repairs and date completed; and
      (6)   Servicing performed and date completed.
   (E)   Whenever backflow prevention devices required by these regulations are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay as required by § 52.88(A).
   (F)   Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without specific authorized by the Superintendent of Water.
   (G)   Each device shall be tested at the time of the installation and at least annually or more frequently if recommended by the manufacturer.
(Ord. 1213, passed 9-7-05)