(a) Individual water riser pipes shall be located within the confined area of the mobile home stand at a point where the water connection will approximate a vertical position.
(b) Water riser pipes shall extend at least four inches above ground elevation. The pipe shall be at least three-quarter inch. The water outlet shall be capped when a mobile home does not occupy the lot.
(c) Adequate provisions shall be made to prevent freezing of service lines, valves and riser pipes and to protect risers from heaving and thawing actions found during freezing weather. Surface drainage shall be diverted from the location of riser pipe.
(d) A shutoff valve below the frost line shall be provided near the water riser pipe on each mobile home lot.
(e) Underground stop and waste valves shall not be installed on any water service.
(Ord. No. 711, 11-11-69)