§ 159-2.315 EXTERIOR LIGHTING PLAN.
   (A)   Authority: Lighting plans and related plans and data must be submitted to the Zoning Administrator who will transmit all lighting plan review applications and their accompanying lighting plans and related plans and data to the Plan Commission, or the Village Engineer as the case may be.
   (B)   Purpose: Except where superseded by a Village approved annexation agreement, lighting plans are required as an integral part of site plan review process.
   (C)   Application: Applications for lighting plan review must be filed in accordance with the requirements of § 159-2.201 of this part and the administrative application policy.
   (D)   Process: Where required, a lighting plan review will be subject to the site plan review process set forth in § 159-2.312 of this part.
   (E)   Lighting Plan Elements: A lighting plan submitted pursuant to this chapter must have, at a minimum, the following elements:
      (1)   A catalog page, cut sheet, or photograph of the luminaire including the mounting method.
      (2)   A photometric data test report of the proposed luminaire graphically showing the lighting distribution at all angles vertically and horizontally around the luminaire.
      (3)   A plot plan, drawn to a recognized engineering or architectural scale, indicating the location of the luminaire(s) proposed, mounting, and/or installation height in feet, the overall illumination levels (in foot-candles) and uniformities on the site, and the illumination levels (in foot-candles) at the property boundary lines. This may be accomplished by means of an isolux curve or computer printout projecting the illumination levels.
      (4)   A graphic depiction of the luminaire lamp (or bulb) concealment and light cutoff angles.
(Ord. 17-2-2065, passed 2-27-2017)