All corridors that serve more than one exit shall provide direct connection to such exits. The length of a dead-end corridor shall not exceed thirty-five feet (10,668 mm) where the building is not equipped throughout with an automatic sprinkler system. The dead-end travel distance limitation shall be increased to seventy feet (21,336 mm) where the building is equipped throughout with an automatic sprinkler system.