3.5.9  Manhole and Cleanout Requirements.
   Connected manholes shall not be separated by more than 500'. In addition, a manhole shall be placed at every location where changes in pipe size, pipe type, pipe direction, or intersection of other connecting pipes (other than single service laterals) occurs. A terminal manhole at the far upstream end of a line can be replaced by a cleanout if the cleanout is within 250' of the downstream manhole. The following chart shall determine manhole inside diameter.
 
Maximum Pipe Size Connected to Manhole (inch OD)
Inside Minimum Diameter of Manhole (feet)
18" and less
4.0
21" - 27"
5.0
30" - 36"
6.0
39" and greater
As Directed by City Engineer
 
   Manholes in the floodplain, or in areas normally subject to runoff water flows, shall have a waterproof seal in the top. Areas subject to known vandalism shall have bolt-down lids.