Six inch or smaller dead end mains are prohibited. All other dead end mains shall be capable of supplying the required fire flow, and shall meet IAWC and/or NFPA 24 requirements and be approved. Buildings having a required fire flow of 3500 gpm or more shall have hydrants served by a main that loops the building or complex of buildings and reconnects back into a distribution supply main in a separate location.
(Ord. 6569, passed 12-8-08) Penalty, see § 94.99