(A) Structure must be non-habitable;
(B) must be anchored to resist floatation forces;
(C) Will require flood openings/vents no more than 1 foot above grade, total openings are to be 1 square inch per 1 square foot of floor area, at least 2 openings required on opposite walls;
(D) Built of flood resistant materials below a level 2 feet above the base flood elevation;
(E) Must elevate utilities above the base flood elevation;
(F) Can only be used for storage or parking;
(G) Cannot be modified for a different use after permitting.
(Ord. passed 10-14-2008; Am. Ord. passed 5-31-2011)