1314.08 SANITARY SEWERS.
   (a)   Every effort shall be made by the developer to minimize infiltration and inflow of unnecessary water into the sanitary sewers. Such efforts shall be the installation of water type manhole covers, chimney seals and other devices to exclude I/I. All such devices shall be approved by the Director of Water/Wastewater.
   (b)   Materials of construction, design and installation of sewers, manholes and covers shall be determined and approved by the Director of Water/Wastewater.
   (c)   The sewer main shall not be less than eight inches outside diameter and each service lateral shall not be less than four inches outside diameter.
   (d)   Manholes shall be installed at: not more than 400 feet apart; all terminations; all significant changes in grade; all changes in flow direction; and all changes in size of pipe.
   (e)   All lots shall be provided with "wyes" or "tees" at the time the main is constructed. Such "wyes" and "tees" not intended for immediate connection shall be plugged using a water tight and noncorrosive, removable plug approved by the Director of Water/Wastewater.
   (f)   The owner or developer shall pay the sewer connection fee when the lot is developed.
   (g)   All building sanitary sewers shall conform to Chapter 925.
   (h)   All dwellings shall have a watertight, sanitary sewer cleanout installed at a distance of four feet from the foundation of the building to facilitate maintenance of the lot.
(Ord. 76-91. Passed 11-11-91.)