(A) The Commission will furnish and connect a meter for each customer and this meter shall remain the property of the Commission.
(B) Where service is provided from intermediate or high pressure lines the Commission will furnish the necessary pressure regulator and this pressure regulator shall remain the property of the Commission.
(C) A suitable vent, terminating in an insect and rainproof fitting, shall be provided for all service pressure regulators.
(D) Service pressure regulators when incorporating a relief device and installed inside shall be vented to the outside to a safe location using 3/4-inch pipe.
(E) Service pressure regulators that do not incorporate a relief device and are installed inside shall be vented to the outside to a safe location using 1/4-inch pipe or 3/8-inch metal tubing.
(F) Any changes or alterations in piping, connecting, and/or reconnecting must be made only by the Commission or an authorized representative of the Commission.