(A) All water main extensions shall be sized to provide for adequate fire flow.
(B) All fire hydrants shall be conveyed to the city by an approved instrument of dedication; and all costs of necessary rental, maintenance and operation of fire hydrants, after acceptance of such dedication, shall be the responsibility of the city.
(C) Each hydrant shall be capable of delivering not less than 500 gpm with a residual pressure of not less than 20 psi.
(D) Fire hydrant branches (from main to hydrant) will be not less than six inches in diameter and as short as possible with a maximum of 300 feet. Each branch will be individually gate valved. On prestressed concrete mains where the installation of fire hydrants is not required immediately, the necessary fitting for the future installation of fire hydrants shall be provided.
('72 Code, § 36-80) (Ord. O-72-206, passed 12-6-72)