§ 158.056 ACCESSORY STRUCTURES.
   Relief to the elevation or dry floodproofing standards may be granted for accessory structures containing no more than 600 square feet. Such structures must meet the following standards:
   (A)   They shall not be used for human habitation;
   (B)   They shall be constructed of flood-resistant materials;
   (C)   They shall be constructed and placed on the lot to offer the minimum resistance to the flow of flood waters;
   (D)   They shall be firmly anchored to prevent flotation;
   (E)   Service facilities such as electrical and heating equipment shall be elevated or floodproofed to or above the level of the flood protection elevation; and
   (F)   They shall meet the opening requirements of § 158.054(E)(3).
(1982 Code, § 158.46) (Ord. 2011-1, passed 2-14-2011)