155.17    GLAZING ADJACENT TO DOORS.
   The Hiawatha Building Code is hereby amended by repealing Sections R308.4.2 of the International Residential Code, and by replacing said section with a new Section R308.4.2 as follows:
   R308.4.2 Glazing adjacent to doors. Glazing in an individual fixed or operable panel adjacent to a door where the nearest vertical edge of the glazing is within a 24-inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the floor or walking surface shall be considered to be a hazardous location.
   Exceptions:
   1. Decorative glazing.
   2. Where there is an intervening wall or other permanent barrier between the door and the glazing.
   3. Where access through the door is to a closet or storage area 3 feet or less in depth. Glazing in this application shall comply with Section R308.4.3.
   4. Glazing that is adjacent to the fixed panel of patio doors.