6-1-7   FIRE CODE; AMENDMENTS.
   The following provisions shall further apply and shall supersede any and all references listed within the adopted edition of the International Fire Code - 2003 Edition.
   (A)   Additions, Insertions and Changes.
      (1)   Section 101.1 - Insert “Village of Hecker”.
      (2)   Section 105 Permits Delete the section in its entirety.
      (3)   Section 108 Delete the section in its entirety and insert the following: The Village Board shall be the Board of Appeals.
      (4)   Section 109.3 Delete the section and add the following: The penalties shall be found in Section 1-1-20 of the Village Code.
      (5)   Section 111.3 Failure to Comply - Delete the last two lines and insert the following:…or unsafe condition, shall be liable for a fine as established by the Section 1-1-20 of the Village Code.
      (6)   Section 505.1 Address numbers delete in the sixth line: or alphabet letters.
      (7)   Add section 903.7 Sprinkler system design criteria. Sprinkler hydraulic designs for NFPA 13 and NFPA 13R systems shall be designed with a minimum of a five (5) pound difference between the sprinkler system design including hose requirements and the available water supply. The five (5) pound safety factor shall be applied to the water flow test after any adjustments for a seasonal low.
      (8)   Section 3204.3.1.1 Fire Department should determine the requirement.
      (9)   Section 3404.2.9.5.1 Fire Department should determine the requirements.
      (10)   Section 3406.2.4.4 Fire Department should determine the requirement.
      (11)   Section 3804.2 Fire Department should determine the requirement.
      (12)   Reference Standards
      Delete the reference to the ICC Electric Code
      Delete the references to the International Plumbing Code in sections 903.3.5, 912.5, 221.2.3, 2704.2.2.6 and insert the Illinois Plumbing Code.
      Adopt the Appendix D Fire Apparatus Access Roads.