§ 92.25 UNDERGROUND AND ABOVEGROUND CONTAINERS.
   (A)   No underground or aboveground storage container for flammable gases other than cylinders or drums shall be located, with respect to the size of the container, closer than the following distances to any building or property line:
 
Water Capacity (per Container)
Minimum Distance
Underground
Aboveground
Less than 125 gallons
10 feet
None
125 to 500 gallons
10 feet
10 feet
500 to 1,200 gallons
25 feet
25 feet
Over 1,200 gallons
50 feet
50 feet
 
   (B)   Aboveground containers of capacity exceeding those shown in the above table may be installed close to buildings or property lines when specifically approved by the inspection department having jurisdiction.
(Prior Code, § 18.16.110) (Ord. 139, passed - -1946) Penalty, see § 92.99