(A) In all SFHAs, relief to the elevation or dry floodproofing standards may be granted for accessory structures.
(B) Such structures must meet the following standards:
(1) Shall not be used for human habitation;
(2) Shall be constructed of flood-resistant materials;
(3) Shall be constructed and placed on the lot so as to offer minimum resistance to the flow of floodwaters;
(4) Shall be firmly anchored to prevent flotation;
(5) Service facilities such as electrical and heating equipment shall be elevated or floodproofed to or above the FPG; and
(6) Shall be designed to allow for the entry and exit of floodwaters to automatically equalize hydrostatic flood forces on exterior walls as required for elevated structures in § 153.39 of this chapter.