No user shall discharge wastewater containing any of the following pollutants in excess of the following interim pollutant discharge limitations:
(A) Compatible pollutants.
(1) Any fats, oil or grease (FOG) in concentrations greater than 1,500 mg/l based on an average of all samples collected within a 24-hour period.
(2) Any total suspended solids (TSS) in concentrations greater than 7,500 mg/l.
(3) Any biochemical oxygen demand (BOD) in concentrations greater than 7,500 mg/l.
(4) Any phosphorus (P) in concentrations greater than 250 mg/l.
Unless otherwise stated, all limitations are based upon samples collected over an operating period representative of a user’s discharge, and in accordance with 40 C.F.R. Part 146.
(B) Non-compatible pollutants cadmium (Cd), 1.0 mg/l.
(Ord. 2009-4, passed 6-23-2009)