§ 51.39 TECHNICAL REQUIREMENTS FOR CUSTOMER OWNED GENERATION.
   (A)   General. The installation shall comply with all applicable land use, zoning, planning, borough ordinances, rules, regulations and the applicable electric classification and rates. The terms and conditions contained herein are in addition to, but do not modify nor negate the terms of the borough ordinances.
   (B)   Fees. For all customer owned generation, the following fees shall apply:
      (1)   Application fee: $200;
      (2)   Interconnection study fee: at cost;
      (3)   Initial inspection fee: $600;
      (4)   Customer shall be responsible for costs of all system studies and upgrades, required to accommodate generation. Customer shall be responsible for annual system testing, witnessed by representatives of the borough;
      (5)   The fixed annual reconciliation period shall be set as June through May; and
      (6)   The customer-generator operating an electric generating facility shall maintain homeowners, commercial or other insurance providing coverage in the amount of at least $1,000,000 for the liability of the insured against losses or damages arising from the use of the customer’s electric generating facility. The borough shall be named an additional insured. The customer must submit evidence of such insurance to the borough before interconnection with the borough system. The borough’s receipt of evidence of liability insurance shall not imply an endorsement of the terms and conditions of the coverage.
   (C)   Purpose. The purpose of this document is to state the terms and conditions that govern the interconnection and operation of on-site distributed generation, in order to:
      (1)   Establish technical requirements which will promote the safe and reliable parallel operation of distributed generation resources;
      (2)   Enhance the reliability of electric service;
      (3)   Facilitate the implementation and use of distributed resources technologies;
      (4)   Enhance economic efficiency in the production and consumption of electricity and other energy; and
      (5)   Promote the use of distributed resources in order to provide electric system benefits during periods of capacity constraint.
   (D)   Applicability. Unless otherwise provided, these guidelines apply to all customer generation interconnected and operated in the borough power delivery system.
   (E)   Definitions. For the purpose of this section, the following definitions shall apply unless the context clearly indicates or requires a different meaning.
      ACCOUNT. One metered or un-metered rate or service classification which normally has one electric delivery point of service. Each ACCOUNT shall have only one electric service supplier which shall be the Borough of Grove City, providing full electric supply requirements for that account.
      COMPANY. Borough of Grove City (hereinafter called borough).
      CUSTOMER.
         (a)   Any adult person, partnership, association, corporation or other entity:
            1.   In whose name a service account is listed;
            2.   Who occupies or is the ratepayer for a premises, building, structure and the like; and
            3.   Who is primarily responsible for payment of bills.
         (b)   A CUSTOMER includes anyone taking electrical service from the borough under one service classification for one account, premises or site. Multiple premises or sites under the same name are considered multiple CUSTOMERS.
      GENERATOR OWNER. The owner of the generating system that is interconnected to the borough electric system. Owner shall be a customer.
      GRID. The interconnected arrangement of lines and transformers that make up the borough electric power system.
      IEEE STANDARD 929-IEEE. Standard entitled Recommended Practice for Utility Interface of Photovoltaic (PV) Systems, latest approved revision thereof.
      IEEE STANDARD 1547-IEEE. Standard entitled IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems.
      INTERCONNECTION. The physical connection of distributed generation to the borough system in accordance with these guidelines so that parallel operation can occur.
      INTERCONNECTION APPLICATION. The letter application which must be submitted by the generation owner to the borough for permission to interconnect with the borough system.
      INVERTER. A static power converter with control, protection and filtering functions that converts direct current input to alternating current output. INVERTERS must be of the non-islanding type.
      ISLAND. A portion of the utility system which contains both load and distributed generation and is isolated from the remainder of the utility system.
      ON-SITE DISTRIBUTED GENERATION. An electrical generating unit which may be connected to the borough electric system. The maximum size allowed for any customer generator system shall not be in excess of 100 kilowatts.
      PARALLEL OPERATION. Any electrical connection between the borough system and the generator owner’s generating source.
      POINT OF COMMON COUPLING. The point where the electrical conductors of the borough system are connected to the customer’s conductors and where any transfer of electric power between the generator owner and the borough electric system takes place.
      PRE-INTERCONNECTION STUDY. A study or studies which may be undertaken by the borough in response to its receipt of a completed application for parallel operation with the borough’s system. PRE-INTERCONNECTION STUDIES may include, but are not limited to, service studies, coordination studies and facilities impact studies. Applicant shall be responsible for all study costs.
      STABILIZED. The borough’s system following a disturbance which returns to the normal range of voltage and frequency for at least five minutes or longer as coordinated with the borough. The borough may require a longer period upon a reasonable showing that the reconnection after five minutes will adversely affect the safety and reliability of the electric system.
      UL 1741. Underwriters Laboratories Inc., document entitled Inverters, Converters, Controllers and Interconnection System Equipment for Use with Distributed Energy Resources.
      UNIT. A distributed generation facility.
      UTILITY SYSTEM OR ELECTRIC DISTRIBUTION FACILITY. Borough’s distribution system operating to which the generation equipment is interconnected.
   (F)   Interconnection application. A proposed generator owner shall make a written letter application to the borough for the interconnection of a generator to the borough system. The customer shall submit a letter to the borough stating the technical aspects of the installation, two clean copies of equipment catalog cuts and two copies of a one line or riser diagram of the proposed installation and interconnection to the borough system. Additionally, a statement by the customer that the installation will be constructed and operated in full compliance with the borough requirements shall be included. For inverter installations, a statement that the inverter for the project is of the non-islanding type to prevent back feeds shall also be included.
   (G)   Designation of borough contact persons for matters relating to distributed generation interconnection. The Borough Office will be the designated point of contact for all matters related to interconnected generation. The borough office will maintain records concerning applications received for interconnection and parallel operation of distributed generation. Such records will include the date of receipt of each such application, documents generated in the course of processing such applications, correspondence regarding such applications and the final disposition of such application.
   (H)   Pre-interconnection studies.
      (1)   Generally. The borough reserves the right to conduct a service study, coordination study or facilities impact study prior to approval of a distributed generation unit. In instances where such studies are deemed necessary, the scope of such studies shall be based on the characteristics of the particular distributed generation unit to be interconnected and the proposed point of interconnection.
      (2)   Completion of pre-interconnection study. Upon completion of the interconnection study, the borough will notify the generator owner that the application has been approved or indicate why the application cannot be approved.
   (I)   Interconnection of distributed generation. Where generation is capable of exporting power to borough system, the interconnection study may result in more stringent interconnection requirements.
   (J)   Pre-approval of generation units, devices and systems. Upon approval by the borough that certain generating unit’s protective devices and/or system(s) meet the standards set out in these guidelines, such approval shall be made available to the appropriate manufacturer upon written request.
   (K)   Connection approval. The generator owner can connect his or her generation to the borough system only after the interconnection application has been approved, the installation has been inspected by the borough, the system has been tested and the tests witnessed by the borough, and the generation owner has received approval notification.
   (L)   Interconnected generation site warning label. The generator owner will install a warning label in a conspicuous place on his or her electric meter or meter box to notify the borough personnel that there is a generator source installed on the load side of the meter. The warning label shall not be placed in a location that would interfere with the ability of borough personnel to read the electric meter. The warning label must be placed before the generation can be interconnected.
   (M)   Disconnection and reconnection. The borough may disconnect a distributed generation unit under the following conditions:
      (1)   Application termination. Upon termination of the approved interconnection application;
      (2)   Noncompliance. For noncompliance with the technical guidelines specified in this document or other requirement contained in the borough ordinance, provided that the borough has given notice to the generator owner and provided the generator owner reasonable time (consistent with the condition) to correct such noncompliance. The borough will reconnect the unit only upon receipt of certification from the generator owner and verification by the borough that the unit is in compliance. The borough will provide verification within a reasonable time period;
      (3)   In case of a system emergency outage of the borough electrical system. The generator owner’s generation equipment must be installed and configured so that parallel operation must automatically cease immediately and automatically during outages or loss of the borough electric source in accordance with these guidelines. The generation owner must also cease parallel operation upon notification by the borough of a system emergency, abnormal condition or in cases where such operation is determined to be unsafe, interferes with the supply of service to other customers or interferes with the borough’s system maintenance or operation. In addition, the borough may disconnect the generator from the system for system emergencies without notice; and
      (4)   For routine maintenance and repairs. The borough may disconnect a customer/generation owner for routine maintenance and repairs on the borough system.
   (N)   Termination. The generation owner may terminate the approved interconnection application upon 30 days’ written notice to the borough. The generator owner must give the borough notice that it intends to permanently shut down his or her generation.
   (O)   Privileged communications concerning proposed distributed generation projects. In the course of processing applications for parallel operation and in the conduct of pre-interconnection studies, the generation owner shall provide the borough with detailed information concerning the proposed distributed generation project and note as privileged, on each applicable sheet and information considered privileged. If any submitted information is requested by a third party, notice shall be given by the borough to the generator owner. It shall be the responsibility of the generation owner to legally challenge the release of this information.
   (P)   Technical guidelines for parallel operation of on-site distributed generation units.
      (1)   This division (P) describes minimum requirements and procedures for safe and effective connection and operation of distributed generation. A generator owner may operate 60 Hertz, three phase or single phase generating equipment, in parallel with the borough’s system pursuant to an approved interconnection application provided that the equipment and generator owner meet or exceed the requirements of these guidelines and that the borough has approved the generator owner’s application to interconnect. This division (P) describes typical interconnection requirements. Certain specific interconnection locations and conditions may require the installations of additional protective settings or hardware, especially when exporting power to the system. If the borough, in the borough’s sole opinion, concludes that an application for parallel operation requires additional protective settings or hardware, the borough shall make those requirements known after all pertinent studies are completed.
      (2)   Approval to connect to the borough system indicates only that the minimum borough electrical requirements for a safe proper interconnection have been satisfied. Such approval does not imply that the generator owner’s facility meets land use, zoning, planning or federal, state and other borough standards or regulations.
         (a)   General interconnection and protection requirements.
            1.   The generator owner’s generation and interconnection installation must meet all borough land use, zoning, planning and applicable national, state and local construction and safety codes.
            2.   The generator owner’s generator shall be equipped with protective hardware and software designed to prevent the generator from energizing the borough’s de-energized circuits. The generator must automatically disconnect from the borough’s system if the grid source is lost, irrespectively of connected loads or other generators.
            3.   The generator shall be equipped with the necessary protective hardware and software designed to prevent sustained parallel operation of the generating equipment with the borough system unless the system service voltage and frequency are within acceptable magnitudes.
            4.   The generator owner will be responsible for protecting its own generating and interconnection equipment in such a manner so that borough system outages, short circuits, single phasing conditions or other disturbances including zero sequence currents and ferroresonant over-voltages do not damage the generator owner’s generating equipment. The protective equipment shall also prevent excessive or unnecessary tripping that would adversely affect the borough’s service reliability to other generator owners and customers.
            5.   The generator and interface protection schemes shall be continuously monitored and functioning and the generator shall immediately disconnect from the borough’s system for any condition that would make the protection scheme inoperable.
            6.   The operating power required for the protection and control schemes for the generator and the control power used to disconnect the generator from the borough must not be dependent on local borough power.
            7.   Where multiple generators are connected to the system through a single point of common coupling, the sum of the ratings of the generators will be used to determine the applicability of these guidelines. Protection scheme performance with one or more units off line will be considered.
            8.   Applicable circuit breakers or other interrupting devices at the generator owner’s facility must be capable of interrupting the maximum available fault current at the site, including any contribution from the owner’s generator(s).
            9.   The generator owner will furnish and install a manual disconnect switch which, when opened, will have the effect of isolating the generator from the borough’s system. The disconnect device shall have a visual break appropriate to the voltage level, and shall be mounted on the exterior of the building adjacent to the borough revenue meter accessible to the borough’s personnel at all times, and shall be capable of being locked in the open position via a borough padlock. The borough shall use reasonable efforts to utilize padlocks of a size consistent with typical manufacture’s specifications. The generator owner shall follow the borough’s switching, clearance and tagging procedures.
            10.   The design, procurement, installation and maintenance of the equipment at the generator owner’s site shall be the responsibility of the generator owner at the generator owner’s expense.
            11.   Any necessary enhancements or improvements needed, in the opinion of the borough, within the borough’s system and/or at the customer sites to accommodate the parallel interconnection of the generator owner’s generation will be at the generator owner’s expense.
            12.   The generator owner has full responsibility and liability for the safe and proper operation of their equipment and the power originating from their generator. The generator owner is also responsible for synchronizing their generator(s) with the borough’s system and maintaining a synchronous operation.
            13.   The generator owner must immediately cease parallel operation upon notification by the borough if such operation is determined to be unsafe, interferes with the supply of service to other customers, or interferes with the borough’s system maintenance or operation.
            14.   The borough reserves the right to specify the type of transformer connection that will be employed for all multiphase interface transformers consistent, where reasonable, with the generator owner’s power system.
         (b)   Prevention of generator owner generation interference with the borough system. To eliminate undesirable interference caused by operation of the generator owner’s generating equipment, the generator owner’s generator shall meet the following criteria.
            1.   Voltage. The generating equipment will be operated in such a manner that the voltage levels on the borough’s system are in the same range as if the generating equipment were not connected to the borough’s system. The generator owner shall provide an automatic method of initiating a disconnect sequence of his or her generating equipment from the borough system with set points noted in the table below.
Generating Systems with Inverters up to 30 KW
Generating Systems with Inverters Greater than 30 KW
Non-Inverter or Rotating Machine Generating Systems
Generating Systems with Inverters up to 30 KW
Generating Systems with Inverters Greater than 30 KW
Non-Inverter or Rotating Machine Generating Systems
Trip in 0.16 Second for V < 50%
Trip in 0.16 Second for V < 50%
Trip in 0.16 Second for V < 50%
Trip in 2 Seconds for 50% V < 88%
Trip within 0.1 to 30 Seconds (Default 2.0 Seconds) for 50% < V 88%
Trip in 2.0 Seconds for 50% V < 88%
Trip in 1 Seconds for 110% < V < 120%
Trip within 0.1 to 30 Seconds (Default 1.0 Second) for 110% < V < 120%
Trip in 1.0 Second for 110% < V < 120%
Trip in 0.16 Second for 120% V
Trip in 0.16 Second for 120% V
Trip in 0.16 Second for 120% V
IEEE 1547-2003
(Specific voltage and time delay set points will be determined for each installation. Otherwise inverter default setting will remain.)
(Specific voltage and time delay set points may vary for each installation. Otherwise, the above set points will remain.)
UL 1741-2005
IEEE 1547-2003
IEEE 1547-2003
UL1741-2005
Note: Trip time refers to the time between when the abnormal voltage condition occurs and the generator being disconnected from the borough system.
 
               a.   On three phase generator installations, full three phase voltage sensing shall be employed. Voltages must be sensed on the high side of any interface transformer if the transformer high voltage winding is ungrounded.
               b.   The generator owner may reconnect to the grid when the system voltage returns to normal range and is stabilized as defined in the definitions.
            2.   Flicker. The generator equipment or operation of equipment shall not cause voltage flicker on the borough’s system or to any other borough customer. This flicker shall not exceed the borderline of irritation curve, as defined in IEEE Standard 519-1992, Recommended Practices and Requirements for Harmonic Control in Electric Power Systems. Lower levels of flicker may be required in areas where equipment such as computers and instrumentation are impacted.
            3.   Frequency.
               a.   The operating frequency of the generating equipment shall not deviate more than the values noted in the table below.
Generating Systems with Inverters up to 30 KW
Generating Systems with Inverters Greater than 30 KW
Non-Inverter or Rotating Machine Generating Systems
Generating Systems with Inverters up to 30 KW
Generating Systems with Inverters Greater than 30 KW
Non-Inverter or Rotating Machine Generating Systems
Trip in 0.16 Second for F < 59.3 Hz.
Trip in 0.16 Second for F < 57.0 Hz.
Trip in 0.16 Second for F < 57.0 Hz.
Trip in 0.16 Second for F > 60.5 Hz.
Trip in 0.16-300 Seconds for 57.0 F < 59.8 Hz.
Trip in 0.16-300 Seconds for 57.0 F < 59.8 Hz.
IEEE 1547-2003
Trip in 0.16 Second for F > 60.5 Hz.
Trip in 0.16 Second for F > 60.5 Hz.
UL 1741-2005
Frequency and time delay set points for 57.0—59.8 Hz. will be determined for each specific installation.
Frequency and time delay set points for 57.0—59.8 Hz. will be determined for each specific installation.
IEEE 1547-2003
IEEE 1547-2003
UL 1741-2005
Note: Trip time refers to the time between when the abnormal frequency condition occurs and the generator being disconnected from borough.
 
               b.   The generator owner may reconnect when the system frequency returns to normal range and is stabilized.
            4.   Harmonics.
               a.   Non-linear circuit elements such as inverter can produce harmonics. Per IEEE Standard 519, Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, the total harmonic distortion (THD) voltage shall not exceed 5% of the fundamental 60 Hz frequency nor 3% of the fundamental for any individual harmonic as measured at the location where the customer interfaces with the borough’s system (point of common coupling). In addition, the level of harmonic current that the customer is allowed to inject into the borough’s system shall not exceed that specified in IEEE Std 519. Furthermore, any communication notch shall be limited as defined by IEEE Std 519. The preceding requirements apply to all types of generation systems.
               b.   The generator owner is responsible for the installation of any necessary controls or hardware to limit the voltage and current harmonics generated by his or her equipment to defined levels.
            5.   Power factor.
               a.   The generator must not adversely impact the power factor of the generator owner site. Inverters shall be designed to operate close to unity power factor. The operating power factor of the generator shall be contained within the limits defined in the table below.
 
Generating Systems with Inverters up to 25 KW
Generating Systems with Inverters Greater than 25 KW
Non-Inverter or Rotating Machine Generating Systems
0.85 lagging or leading when output exceeds 10% of inverter rating. (From IEEE 929-2000)
0.85 lagging or leading when output exceeds 10% of inverter rating
0.85 lagging or leading
 
               b.   However, to the extent that a generator owner’s power factor at the point of common coupling falls below 0.985 lagging, the generator owner must obtain, install and maintain, at his or her expense, corrective apparatus that compensates for the drop in power factor caused by the installation of the generator.
            6.   Current.
               a.   In some cases, directional over-current protection may be required to limit fault current flowing onto the grid in the event of a line fault. DC inverters that are incapable of producing fault current do not require directional over-current protection.
               b.   Inverter systems shall not inject DC current greater than 0.5% of rated inverter output in the AC interface point under either normal or abnormal conditions.
            7.   Fault and line clearing. The generator owner shall automatically disconnect from the borough’s system during electrical faults on the borough’s electrical system and upon loss of the borough’s electric source. The generator owner may reconnect when the system voltage and frequency return to normal range and is stabilized. Detection of the loss of the borough’s primary electric system, where the generator owner is operating in an island with other customer load, becomes increasingly difficult as the level of dispersed generation on a feeder approaches the connected load. The over/under voltage and over/under frequency settings described previously along with the anti-islanding provisions of IEEE 929/UL 1746 inverters, shall be sufficient to satisfy this provision.
            8.   Automatic reclosing. The generator owner is responsible for protecting his or her equipment from the effects of switching or automatic reclosing of the borough’s feeder circuits.
      (3)   Control, protection and safety equipment requirements specific to generators of 25 KW or less. All generators 10 KW or less can be single phase. The following table describes necessary control, protection and safety equipment specific to generator of 25 KW or less connected to secondary or primary voltage systems:
Control, Protection and Safety Equipment for Generators of 25 KW1 or Less Connected to Secondary System
Control, Protection and Safety Equipment for Generators of 25 KW1 or Less Connected to Secondary System
Generator size 25 KW or less
Generator disconnect device
Over-current trip
Over-voltage trip
Under voltage trip
Over/under frequency trip
Synchronizing checks2
Manual or automatic
Notes:
1 Exporting to the borough system many require additional operational/protection devices.
2 For synchronous and other type of generators with stand-alone capability.
 
      (4)   Control, protection and safety equipment requirements specific to three phase synchronous generators, induction generators, and inverter systems. Generators greater than 25 KW must be three phase machines connected to three phase circuits.
         (a)   Three phase synchronous generators. Generator circuit breakers shall be three-phase devices with electronic or electromechanical control. The generator owner is solely responsible for properly synchronizing his or her generator with the company’s system. For a synchronous generator, the excitation system response ratio shall not be less than 0.5. The generator’s excitation system(s) shall conform, as near as reasonably achievable, to the field voltage vs. time criteria specified in American National Standards Institute Standard C50.13-1989 in order to permit adequate field forcing during transient conditions.
         (b)   Three phase induction generators and inverter systems. Induction generation may be connected and brought up to synchronous speed (as an induction motor) if it can be demonstrated that the initial voltage drop measured on the company ‘s side at the point of common coupling is within the visible flicker limits. Otherwise, the generator owner may be required to install hardware or other techniques to bring voltage fluctuations to acceptable levels. Line-commutated inverters do not require synchronizing equipment. Self-commutated inverters whether of the utility-interactive type or stand-alone type shall be used in parallel with the company system only with synchronizing equipment.
Control, Protection and Safety Equipment 1 Less than 100 KW Three Phase Connected to Primary System
Control, Protection and Safety Equipment 1 Less than 100 KW Three Phase Connected to Primary System
Generator disconnect device
Over-voltage trip
Under-voltage trip
Over-current trip
Over/under frequency trip
Ground over-voltage trip
Ground over-current trip
Synchronizing check1
Manual or automatic
Excessive closed time trip transfer trip/reclose blocking
Notes:
1 Exporting to the company’s system may require additional operating/protection devices and will require coordination of operations with the company.
 
      (5)   Requirements specific to generators paralleling for 0.1 second or less (closed transition switching). The table below shows the protective functions required by this requirement for generators less than one MW which parallel with the company’s system for 0.1 second or less such as during source or load transfers.
Control, Protection and Safety Equipment Generators Connected to Secondary or Primary System Voltage
For 0.1 Second or Less (Closed Transition Switching)
Control, Protection and Safety Equipment Generators Connected to Secondary or Primary System Voltage
For 0.1 Second or Less (Closed Transition Switching)
Generator size
Up to 1 MW
Over-voltage trip
Under-voltage trip
Synchronizing check
Manual or automatic
Excessive closed time trip
Notes:
1. For synchronous and other types of generators with stand-alone capability.
2. Scheme will trip generator if closed transition parallel mode remains in effect longer than 0.1 second.
 
      (6)   Inverter type. DC generation installations using inverters for interconnection with the borough must use non-islanding type inverters as defined in IEEE 929, IEEE Recommended Practices for Utility Interface of Photovoltaic (PV) Systems (including Annex B, D, E & G) and UL Subject 1741, May 1999, Standard for Static Inverters and Charge Controllers for use in Photovoltaic Power Systems.
      (7)   Inspection and start-up testing. The generator owner shall provide the borough with reasonable prior notice at least three weeks before the initial energizing and start-up testing of the generator owner’s generating equipment and the borough, at its discretion, shall witness the testing of any equipment and protective systems associated with the interconnection. The generator owner shall revise and resubmit the application information for any proposed modification that may affect the safe and reliable operation of the borough’s system. The generator may be reconnected to the borough’s system only after the modified application has been reviewed, testing has been confirmed and the borough has given approval to reconnect.
      (8)   Site testing and commissioning. Testing of protection systems shall include procedures to functionally test all protective elements of the installation up to and including tripping of the generator and interconnection point. Testing and testing intervals shall be in accordance with manufacturers’ and industry recommendations. Testing shall verify all protective set points and relay/breaker trip timing. The borough, at it discretion, may witness the testing of installed switchgear, protection systems, and generator. The generator owner is responsible for all maintenance of the generator, control and protective equipment. The generator owner will maintain records of such maintenance activities which the borough may review at reasonable times. Annual inspection of each generator installation shall be required at the discretion of the borough.
      (9)   Revenue metering. Revenue metering requirements will be reviewed on each specific installation. A single net meter shall be provided by the borough for each generator installation. The customer shall be responsible for all costs associated with the borough revenue metering.
      (10)   Dedicated transformer. A dedicated transformer or other current-limiting device shall be required for any type of generator installation where the increase in available short circuit current could adversely impact other borough customers on the same secondary circuit.
      (11)   Applicable standards. All equipment and installations, and specifically generation installations, shall meet all requirements including, but not limited to, safety and performance, of the current edition of the National Electrical Code, applicable Institute of Electrical and Electronic Engineers’ (IEEE) standards, Underwriters Laboratories, borough’s specific requirements, UL 1741 and IEEE 1547.
   (Q)   Customer owned standby generation.
      (1)   Written authorization and approval. Standby generation shall be allowed with the express written authorization and approval of customer equipment by the borough.
      (2)   Standby generators. Customer may install standby generation to serve all or part of existing load in the event of an interruption in service. Electrical connection between the borough service and the standby generation is prohibited without a borough approved transfer switch. The installation shall comply with all applicable land use, zoning, planning, borough ordinances, borough rules and regulations and the applicable electric classification and rates.
      (3)   Method of installation. The customer shall install an open transition transfer switch so there can be no electrical connection between the borough service and the standby generation. Switch shall be of the break before make type preventing electrical interconnection of the borough service and standby generation. Closed transition switching shall be subject to equipment approval of the borough. Standby generation shall have over current protection integrated with the generator.
      (4)   Transfer switch. The transfer switch may be operated manually or automatically. The transfer switch shall be rated adequately for the voltage, current and interrupting levels.
      (5)   Conditions of National Electrical Code. All installations shall be subject to the requirements of the current edition of the National Electrical Code.
      (6)   Location. It shall be prohibited to operate a generator indoors, in a garage, (attached or detached) or in an appendage to any structure absent compliance with Borough Code and a borough approved exhaust venting system.
      (7)   Consult borough before installation. Customer shall notify the borough prior to installing standby generation.
   (R)   Customer owned portable generation.
      (1)   Portable generation. Customer may install use portable generation to serve selected existing load in the event of an interruption in service. The installation shall comply with all applicable land use, zoning, planning, Borough Code rules and regulations and the applicable electric classification and rates.
      (2)   Allowable. Portable customer owned generation shall be allowed only without electrical connection between the borough service, building electrical service and the portable generation. Closed transition switching is prohibited. Electrical connection between the generation, service, building wiring and outlet connections, shall not be allowed.
(1980 Code, Ch. 8, Part 1, § 78) (Res. 2013-12, passed 6-17-2013)