§ 54.36 SIZE OF FITTINGS.
   (A)   The size of the pipe to be used in piping buildings for gas (other than for the supply of gas engines, instantaneous automatic hot water heaters, hot air furnaces and low pressure steam or circulating water boilers for heating) shall depend upon the number of 3/8 inch openings to be supplied thereby and upon the length or run of the pipe from the supply pipe to the opening. In determining the size of the pipe and maximum length of run thereof for a given number of 3/8 inch openings, the following table shall control:
Openings
Top size of pipe inches, under length of pipe in feet
 
3/8
3/4
1
1
1
2
2
3
Openings
Top size of pipe inches, under length of pipe in feet
 
3/8
3/4
1
1
1
2
2
3
1
20
40
70
100
150
200
300
2
20
60
100
150
200
300
4
10
50
80
150
200
300
6
40
70
150
200
300
400
8
30
60
120
200
300
400
10
50
100
170
300
400
500
14
40
90
140
300
400
500
18
30
70
120
275
400
500
22
50
100
250
350
450
30
30
70
225
300
400
40
25
50
190
250
350
50
40
160
225
300
60
30
130
200
275
76
25
100
175
250
100
75
150
225
126
50
125
200
150
100
150
200
75
100
250
50
75
300
50
400
30
 
   (B)   In applying the foregoing table, the following rules shall prevail, to-wit: one stove outlet, -inch opening; one gas log or other grate fire, 3/4-inch opening; one kitchen range, 3/4-inch opening; one kitchen boiler heater separated from range, -inch opening.
(`85 Code, § 20-64)