§ 151.089 UTILITIES.
   (A)   Electric. All electric utilities to the building side of the meter, both interior and exterior to the building, are regulated by this chapter. Distribution panel boxes must be at least 2 feet above the flood protection elevation. All outlets and electrical installations, such as heat pumps, air conditioners, water heaters, furnaces, generators, distribution systems, must be installed at or above the flood protection elevation.
   (B)   Plumbing. Toilets, sinks, showers, water heaters, pressure tanks, furnaces, and other permanent plumbing installations must be installed at or above the flood protection elevation.
   (C)   Gas. Gas meters, distribution lines, and gas appliances must be installed at or above the flood protection elevation.
   (D)   Water supply and sanitary facilities. Water supply distribution and sanitary disposal collection systems must be designed to minimize or eliminate the infiltration of flood waters into the systems or discharges from the systems into floodwaters and shall be located and constructed so as to minimize or eliminate flood damage. On-site sewage disposal systems including septic tanks, cesspools, seepage pits, and drain fields are prohibited in all floodplain zones.
(Ord. —, passed 10-22-1991; Am. Ord. —, passed 8-20-2013) Penalty, see § 151.999