(A) The requirements of this section shall apply in all zoning districts.
(B) The sound pressure level, to be measured as described in division (D) below, shall not exceed the following decibel levels in the designated octave bands within the designated zoning districts:
Octave Band, Cycles Per Second | Sound Levels in Decibels | |
Agriculture, Office, Commercial and Industrial Districts | Residential Districts |
Octave Band, Cycles Per Second | Sound Levels in Decibels | |
Agriculture, Office, Commercial and Industrial Districts | Residential Districts | |
0 to 75 | 73 | 58 |
76 to 150 | 69 | 54 |
151 to 300 | 65 | 50 |
301 t0 600 | 61 | 46 |
601 to 1,200 | 44 | 40 |
1,201 to 2,400 | 48 | 33 |
2,401 to 4,800 | 41 | 26 |
Over 4,800 | 35 | 20 |
(C) Objectionable sounds of an intermittent nature which are not easily measured shall be controlled so as not to become a nuisance to adjacent uses.
(D) The sound levels shall be measured with a sound level meter and associated octave band filter as prescribed by the American Standards Association.