(A) All combustible material shall be stored in such a way as to include, where necessary, access drives to permit free access of firefighting equipment.
(B) The bulk storage of flammable liquids and chemicals, when stored in above-ground tanks, shall be no closer to the lot line or any principal building than the distance indicated below:
Capacity Per Container (Gallons) | Minimum Separation Distance |
Capacity Per Container (Gallons) | Minimum Separation Distance |
Less than 125 | None |
125 to 250 | 10 feet |
251 5o 500 | 10 feet |
501 to 2,000 | 25 feet |
2,001 to 30,000 | 50 feet |
30,001 to 70,000 | 75 feet |
70,001 to 90,000 | 100 feet |
(C) The underground bulk storage of flammable liquids shall be located in accordance with the city Fire Code regarding tank storage underground, except the minimum distance between such underground tanks and any residential zone boundary shall be at least ten feet.
(Ord. O-05-04, passed 4-11-05)